What Happens When Your Dust Collector’s Exhaust Goes Outside?
Fall is here! While some people are happy to escape the summer heat, others are dreading the approach of icy temperatures. Furnaces and unit heaters that have sat idle since spring are about to kick back on, and if your dust collection system vents outdoors, an extra expense is about to start adding up.
Many dust collection systems are configured to exhaust outdoors. That means your dust collector removes more than just dust: It moves air, your shop’s conditioned air, out of the building. And it does so continuously as the minutes turn into hours and days of lost heat. It’s easy to ignore in the summer, but once the temperature drops, that same airflow means heated air blowing straight outside (fast!) and replaced by cold air that you have to pay to warm up.
What Makeup Air Means
Makeup air is the outdoor air that replaces whatever your system exhausts outside. A dust collector configured for external exhaust removes a large volume of air from the building. That air has to be replaced from somewhere, just as blowing air out of a straw requires blowing air into it.
There are only two ways that this replacement of inside air with outside air happens: a deliberate, engineered supply of outdoor air, or uncontrolled infiltration through whatever gaps, doors, and loading dock seals exist.
Filtered, recirculating configurations don’t have this issue. If cleaned air returns to the shop instead of venting outdoors, there’s no net air volume leaving the building, and no makeup air demand to plan for. The question of makeup air only comes up when a system is configured to exhaust outside.
It’s A Fall Problem
The physics don’t change with the seasons, but your sense of urgency does.
Winter is when every cubic foot of exhausted shop air has to be replaced by a cubic foot of outdoor air, and in a Michigan January, where Clear Vue Cyclones HQ is located, that outdoor air will be entering at 0 Fahrenheit on the really cold days. Something has to heat it back up to shop temperature, whether that’s a dedicated makeup air unit, or the building’s main HVAC system doing it incidentally, and working harder than planned into the bargain.
The Cost of Makeup Air from Externally-exhausted Dust Collectors
If your facility uses a 10,000 CFM system running 5 days a week, unmanaged makeup air can cost tens of thousands of dollars a year in wasted heating. That scales up or down to any larger or smaller externally-exhausted system. And the cost starts accruing the day the furnace kicks on for the first time of the season.
How to Estimate Your Costs
Heating outdoor air to shop temperature follows the formula:
BTUs/hr = 1.08 × CFM × ΔT
where CFM is the exhausted air volume and ΔT is the difference between shop temperature and outdoor temperature, in degrees Fahrenheit.
Here’s an example: a 5,000 CFM exhaust system, a 68°F shop, and a 10°F winter day. That leaves a ΔT of 58°F. That’s roughly 313,000 Btu/hr of heating load just to bring replacement air up to temperature. That’s above and beyond the building’s normal heating requirements. Run that for a full winter and the total is probably going to climb much higher than you would like. Actual figures would, of course, depend on your exhaust volume, local temperatures, run schedule, and fuel cost. If you do have an externally-vented dust collector, it’s worth gathering the specifics you need to estimate upcoming costs for your own specific facility.
Clues That You Have a Makeup Air Problem (Besides Your Bill)
A few things tend to show up before anyone connects them to the dust collector:
- Exterior doors that are hard to open, or that shut on their own
- A significant cold draft, or a significant number of them
- A furnace that runs longer than it should
- Very uneven temperatures between rooms, especially near loading docks or large exterior doors
One note: if the building has any naturally vented, gas-fired equipment, such as water heaters or furnaces, you should know that negative building pressure can pull that equipment’s combustion exhaust back down the flue instead of letting it vent outside as it should. It’s called backdrafting: a real danger for carbon monoxide poisoning. It’s not dust collection-related, but it’s a direct consequence of external venting and the subsequent negative pressure.
Two Ways to Fix It
Switch to a Filtered, Recirculating Configuration
Where your material and local code allow it, this is the most direct fix. Configuring the system with filters instead of external exhaust means cleaned air returns to the shop instead of leaving the building, which removes the makeup air problem entirely.
Install a Properly Sized, Heated Makeup Air Unit
Where exhausting outdoors is required, the answer is a makeup air unit. This removes the strain from your HVAC system, keeping it from absorbing a load it was not sized for.
Don’t Wait Until Thousands of CFM of Heated Air Are Lost
Exhaust configuration is one of the questions Clear Vue’s duct design team asks up front; it’s cheaper to plan your system right the first time than it is to retrofit once the heat’s already escaping.
It’s also a cost that belongs in the same conversation as the rest of a system’s lifetime cost. Clear Vue’s total cost of ownership calculator shows makeup air as its own line item, so you can see an estimate of what an unmanaged exhaust configuration costs over ten years, not just this winter.
If your system vents outdoors and nobody’s run those numbers, now is the time to run them.